User Manual Version 1.0 Owner manual
12-74
SP600 AC Drive User Manual
Displays the present frequency reference scaled as a DPI reference
for peer-to-peer communications. The value shown is the value after
the accel/decel ramp but prior to any corrections supplied by slip
comp, PI, etc.
Disables manual requests at the port corresponding to bit number.
Example of manual mode selection source:
If:
• Bit 0 = 0 (Terminal block disabled)
• Bit 1 = 1 (Local OIM enabled)
Then manual mode selection can be activated from the OIM but not
the I/O terminals.
273 Drive Ramp Rslt
Range: 0 to 32767 [1]
Default: Read Only
Access: 2 Path: Communication>Comm Control
See also:
286 Manual Mask
Range: See figure 12.44
Default: See figure 12.44
Access: 2 Path: Communication>Masks & Owners
See also:
Figure 12.44 – Manual Mask (286)
1
1
x
xxxxx
10 01234567891112131415
1 = Enabled
0 = Disabled
x =Reserved
Bit #
Factory Default Bit Values
Local OIM
DPI Port 2
Nibble 1Nibble 2Nibble 3Nibble 4
x
x
1
Terminal Blk
Reserved
Network
1
1
DPI Port 3
Reserved
xx
x