User Manual Version 1.0 Owner manual

12-68
SP600 AC Drive User Manual
Captures and displays the Drive Status 1 bit pattern at the time of
the last fault. See parameter 209 for the bit descriptions.
Captures and displays the Drive Status 2 bit pattern at the time of
last fault. See parameter 210 for the bit descriptions.
227 Status 1 @ Fault
Range: See figure12.37
Default: Read Only
Access: 2 Path: Utility>Diagnostics
See also: 209, 224-230
Figure 12.37 – Status 1 @ Fault (227)
0110000101110000
10 01234567891112131415
1 = Condition True
0 = Condition False
x =Reserved
Bit #
Ready
Active
Command Dir
Actual Dir
Accelerating
Decelerating
Alarm
Faulted
At Speed
Local ID 0
Local ID 1
Local ID 2
Spd Ref ID 0
Spd Ref ID 1
Spd Ref ID 2
Spd Ref ID 3
Nibble 1Nibble 2Nibble 3Nibble 4
228 Status 2 @ Fault
Range: See figure12.38
Default: Read Only
Access: 2 Path: Utility>Diagnostics
See also: 210, 224-230
Figure 12.38 – Status 2 @ Fault (228)
0000000x000000xx
10 01234567891112131415
1 = Condition True
0 = Condition False
x =Reserved
Bit #
Ready
Active
Running
Jogging
Stopping
DC Braking
AutoTuning
AutoRst Ctdn
AutoRst Act
Curr Limit
Bus Freq Reg
Motor Overld
DPI at 500 k
Nibble 1Nibble 2Nibble 3Nibble 4