User Manual Version 1.0 Owner manual

12-66
SP600 AC Drive User Manual
Displays the current state of the digital outputs.
Displays the present operating temperature of the drive power
section.
Displays the accumulated percentage of drive overload.
Continuously operating the drive over 100% of its rating will
increase the value of Drive OL Count to 100% and cause a drive
fault or foldback depending on the setting of Drive OL Mode (150).
217 Dig Out Status
Range: See figure12.36
Default: Read Only
Access: 2 Path: Utility>Diagnostics
Inputs & Outputs>Digital Outputs
See also: 380-384
Figure 12.36 – Dig Out Status (217)
0xx 0xxxxxxxxxxxx
10 01234567891112131415
1 = Output Energized
0 = Output De-energized
x =Reserved
Bit #
Digital Out1
Digital Out2
Nibble 1Nibble 2Nibble 3Nibble 4
Function Terminal
Digital Out1 Relay 1, NO, 11/12
Relay 1, NC, 12/13
Digital Out2 Relay 2, NO, 24/25
Relay 2, NC, 25/26
218 Drive Temp
Range: -/+100 degC [0.1 degC]
Default: Read Only
Access: 2 Path: Utility>Diagnostics
See also:
219 Drive OL Count
Range: 0.0 to 100.0% [0.1%]
Default: Read Only
Access: 2 Path: Utility>Diagnostics
See also: 150