User Manual Version 1.0 Owner manual
12-64
SP600 AC Drive User Manual
Displays the source of the speed reference of the drive.
Displays the inputs currently preventing the drive from starting.
213 Speed Ref Source
Range: 0 = PI Output
1 = Analog In 1
2 = Analog In 2
3-8 = Reserved
9 = MOP Level
10 = Jog Speed
11 = Preset Spd 1
12 = Preset Spd 2
13 = Preset Spd 3
14 = Preset Spd 4
15 = Preset Spd 5
16 = Preset Spd 6
17 = Preset Spd 7
18 = Local OIM
19 = DPI Port 2
20 = DPI Port 3
21 = Reserved
22 = Network
23 = Reserved
Default: Read Only
Access: 2 Path: Utility>Diagnostics
See also: 90, 96, 101
214 Start Inhibits
Range: See figure12.34
Default: Read Only
Access: 2 Path: Utility>Diagnostics
See also:
Figure 12.34 – Start Inhibits (214)
0001100x1000x0xx
10 01234567891112131415
1 = Inhibit True
0 = Inhibit False
x =Reserved
Bit #
Fault
Type 2 Alarm
Enable
DC Bus Pchrg
Stop Asserted
Params Reset
StartUp Actv
Digital In
Local OIM
DPI Port 2
DPI Port 3
Network
Nibble 1Nibble 2Nibble 3Nibble 4