User Manual Version 1.0 Owner manual

Parameter Descriptions
12-63
Indicates Type 1 alarm conditions that currently exist in the drive.
Note that for alarm conditions not configured in Alarm Config 1
(259), the status indicated will be a zero.
See section 13.3 for alarm descriptions.
Indicates Type 2 alarm conditions that currently exist in the drive.
See section 13.3 for alarm descriptions.
211 Drive Alarm 1
Range: See figure12.32
Default: Read Only
Access: 1 Path: Utility>Diagnostics
Utility>Alarms
See also: 212, 259
Figure 12.32 – Drive Alarm 1 (211)
00 x000x000xxxxxx
10 01234567891112131415
1 = Condition True
0 = Condition False
x =Reserved
Bit #
Prechrg Actv
UnderVoltage
Power Loss
Reserved
Anlg in Loss
IntDBRes OH
Reserved
Drv OL Lvl 1
Drv OL LVl 2
Decel Inhibit
Nibble 1Nibble 2Nibble 3Nibble 4
212 Drive Alarm 2
Range: See figure12.33
Default: Read Only
Access: 1 Path: Utility>Diagnostics
Utility>Alarms
See also: 211, 230
Figure 12.33 – Drive Alarm 2 (212)
00000000000xx00
10 01234567891112131415
1 =Condition True
0 =Condition False
x =Reserved
Bit #
DigIn CflctA
DigIn CflctB
DigIn CflctC
Bipolr Cflct
MtrTyp Cflct
NP Hz Cflct
MaxFrq Cflct
VHz NegSlope
IR Vlts Rang
FlxAmps Rang
SpdRef Cflct
Nibble 1Nibble 2Nibble 3Nibble 4
Dig In Value
UserSet Cflct
0