User Manual Version 1.0 Owner manual
12-54
SP600 AC Drive User Manual
Enables a feature to save the present frequency reference value
issued by the OIM. This value is saved to drive memory on power
loss. The value is then restored to the OIM on power up.
Enables/disables a feature to automatically load the present auto
frequency reference value into the OIM when Manual is selected.
This allows smooth speed transition from Auto to Manual; you can
then adjust the manual speed setpoint starting from the transferred
Auto speed level.
0 = Disabled: No preload of the Auto speed setpoint into the
manual setpoint. In this case, the motor reference will switch
automatically to the internal Manual setpoint.
1 = Enabled: The Manual setpoint will be loaded with the present
running speed.
192 Save OIM Ref
Range: See figure 12.25
Default: See figure 12.25
Access: 2 Path: Utility>OIM Ref Config
See also:
Figure 12.25 – Save OIM Ref (192)
xxx 1xxxxxxxxxxxx
10 01234567891112131415
1 =Save
0 = Do Not Save
x =Reserved
Bit #
Factory Default Bit Values
At Powr Down
Nibble 1Nibble 2Nibble 3Nibble 4
193 Man Ref Preload
Range: 0 = Disabled
1 = Enabled
Default: 1 = Enabled
Access: 2 Path: Utility>OIM Ref Config
See also: 320 - 327, 361 - 366