User Manual Version 1.0 Owner manual
12-44
SP600 AC Drive User Manual
Sets the amount of time DC brake current is “injected” into the
motor.
Sets the responsiveness of the bus regulator. Adjust the value to
improve performance of the bus regulator to prevent nuisance
overvoltage (bus) faults.
159 DC Brake Time
Range: 0.0 to 90.0 Sec [0.1 Sec]
Default: 0.0 Sec
Access: 1 Path: Dynamic Control>Stop/Brake Modes
See also: 155 - 158
160 Bus Reg Gain
Range: 0 to 5000 [1]
Default: 450
Access: 2 Path: Dynamic Control>Stop/Brake Modes
See also: 161, 162