User Manual Version 1.0 Owner manual

12-28
SP600 AC Drive User Manual
Specifies if Ref A speed reference is to be trimmed.
Analog reference scaling. Scales the upper value of the Trim In
Select (117) selection when the source is an analog input. This
value should be set in conjunction with Analog In 1 Hi (322) or
Analog In 2 Hi (325). See figure 12.51.
Analog reference scaling. Scales the lower value of the Trim In
Select (117) selection when the source is an analog input. This
value should be set in conjunction with Analog In 1 Lo (323) or
Analog In 2 Lo (326). See figure 12.51.
118 Trim Out Select
Range: See figure 12.12
Default: See figure 12.12
Access: 2 Path: Speed Command>Speed Trim
See also: 117, 119, 120
Figure 12.12 – Trim Out Select (118)
xxx 0xxxxxxxxxxxx
10 01234567891112131415
1 = Trimmed
0 = Not Trimmed
x =Reserved
Bit #
Factory Default Bit Values
Trim Ref A
Nibble 1Nibble 2Nibble 3Nibble 4
119 Trim Hi
Range: -/+ Maximum Speed [0.1 Hz]
Default: 60.0 Hz
Access: 2 Path: Speed Command>Speed Trim
See also: 82, 117
120 Trim Lo
Range: -/+ Maximum Speed [0.1 Hz]
Default: 0.0 Hz
Access: 2 Path: Speed Command>Speed Trim
See also: 117