User Manual Version 1.0 Owner manual
12-26
SP600 AC Drive User Manual
Analog input reference scaling. Scales the lower value of the TB
Man Ref Sel (96) selection when the source is an analog input.
Parameter 98 should be set in conjunction with Analog In 1 Lo (323)
or Analog In 2 Lo (326) depending on the appropriate analog input
used. See figure 12.51.
Sets the output frequency when a jog command is issued. The jog
function can be activated from the terminal block or OIM keypad.
Provides an internal fixed speed command value when
Speed Ref A is set to one of the Preset Speed (1-7) internal
references. Alternatively, one of the internal preset speed setpoint
values can be selected via logic control if any of the Digital In
x
Sel
(361-366) are configured to be Speed Sel 1, 2, or 3.
98 TB Man Ref Lo
Range: -/+ Maximum Speed [0.1 Hz]
Default: 0.0 Hz
Access: 1 Path: Speed Command>Speed References
See also: 96
100 Jog Speed
Range: -/+ Maximum Speed [0.1 Hz]
Default: 10.0 Hz
Access: 0 Path: Speed Command>Discrete Speeds
See also:
101
102
103
104
105
106
107
Preset Speed 1
Preset Speed 2
Preset Speed 3
Preset Speed 4
Preset Speed 5
Preset Speed 6
Preset Speed 7
Range: -/+ Maximum Speed [0.1 Hz]
Default: See table 12.2
Access: 101=0
102 -107=2
Path: Speed Command>Discrete Speeds
See also: 90
Table 12.2 – Default Values for Preset Speeds 1-7
Parameter No. Parameter Name Default
101 Preset Speed 1 5.0 Hz
102 Preset Speed 2 10.0 Hz
103 Preset Speed 3 20.0 Hz
104 Preset Speed 4 30.0 Hz
105 Preset Speed 5 40.0 Hz
106 Preset Speed 6 50.0 Hz
107 Preset Speed 7 60.0 Hz