User Manual Version 1.0 Owner manual
Parameter Descriptions
12-7
Displays the setpoint value of the signal at the MOP
(Motor-Operated Potentiometer) function. The setpoint can be
retained after power down or stop by setting parameter 194.
Displays the present DC bus voltage level.
Displays a six-minute average of the DC bus voltage level.
Displays the value of the signal at the analog inputs. This value
does not include user-programmed scaling information (for
example, Analog In1 Hi). The value displayed depends on the
setting of Analog In Config (320).
11 MOP Frequency
Range: +/- 400.0 [0.1 Hz]
Default: Read Only
Access: 1 Path: Monitor>Metering
See also: 194, 195
12 DC Bus Voltage
Range: Voltage rating-dependent [0.1 VDC]
Default: Read Only
Access: 1 Path: Monitor>Metering
See also:
13 DC Bus Memory
Range: Voltage rating-dependent [0.1 VDC]
Default: Read Only
Access: 2 Path: Monitor>Metering
See also:
16
17
Analog In1 Value
Analog In2 Value
Range: 4.000 to 20.000 mA [0.001 mA]
-/+10.0 V [0.1 V]
Default: Read Only
Access: 1 Path: Monitor>Metering
See also: 320
Value of:
If Parameter 320
=.xx00
If Parameter 320 =
.xx11
Analog In1 volts (terminals 14/15) mA (terminals 16/17)
Analog In2 volts (terminals 18/19) mA (terminals 20/21)