Installation and Operation Manual Owner manual
5-6
SP500 AC Drive Installation and Operation Manual Version 3.1
Multi-Speed Preset Wiring
Multi-speed preset wiring connects to terminals 6 through 8, and 11. See figure 5.7.
When control type 3 is selected through parameter F-00, remote terminal strip control
is enabled with multi-speed presets. This mode of operation changes the functionality
of terminals 6 through 8 and may be used in place of 2- and 3-wire start/stop wiring.
See figure 5.8.
When you enable multi-speed preset operation, the state of terminals 7 and 8
determine the source of the speed reference:
Terminal 7 Terminal 8 Speed Reference Source
0 0 Terminal Strip Analog Input
0 1 Multi-Speed Preset 1 (Parameter F-23)
1 0 Multi-Speed Preset 2 (Parameter F-24)
1 1 Multi-Speed Preset 3 (Parameter F-25)
Figure 5.7 – Multi-Speed Preset Sample Control Wiring
Start/Stop/IET Reset
Multi-Speed Preset 1
Fwd
Rev
Function
Loss
Customer
Interlock
Multi-Speed Preset 2
Start/Stop/IET Reset
Multi-Speed Preset 2
Multi-Speed Preset 1
Forward/Reverse
Function Loss
24 VDC Common