Installation and Operation Manual Owner manual
Record of User Settings
B-1
APPENDIX B
Record of User Settings
Parameter
No. Parameter Name Range Step Size
Default
Setting Setting Date
F-00 Control Source Select 0, 1, 2, 3 N/A 0
F-01 Accel Time (seconds) 0.5 - 90.0 0.10 5.0
F-02 Decel Time (seconds) 0.5 - 90.0 0.10 5.0
F-03 Minimum Speed (Hz) 0.5 - 30.0 0.10/0.25 5.0
F-04 Maximum Speed (Hz) 30.0 - 240.0 0.10/0.25 60.0
F-05 Current Limit (%) 10 - 150 1.0 150
F-06 Manual Torque Boost (%) 2 - 10 1.0 2
F-07 V/Hz Base Speed (Hz) 3 - 240 1.0 60
F-08 RPM at Base Speed 10 - 9999 1.0 1750
F-09 Configurable Output Relay Select 0, 1, 2 N/A 0
F-10 Carrier Frequency (kHz) 4, 6, 8 N/A 4
F-11 Remote Reference Gain (%) 60 - 100 0.10 100
F-12 Remote Reference Offset (%) 0 - 40 0.10 0
F-13 Percent Selected Speed
Reference Display Enable
ON, OFF N/A OFF
F-14 Electronic Thermal Overload (%) 20 - 100 1.0 100
F-15 Electronic Thermal Overload
Enable
ON, OFF N/A ON
F-16 Coast Stop Enable ON, OFF N/A ON
F-17 Reverse Disable ON, OFF N/A OFF
F-18 RPM Setpoint Enable ON, OFF N/A OFF
F-19 Power-Up Start Enable ON, OFF N/A OFF
F-20 Password Lockout Enable ON, OFF N/A OFF
F-21 Avoidance Frequency (Hz) Min speed -
Max speed
0.10 5
F-22 Avoidance Bandwidth (Hz) 0.0 - 30.0 0.10 0
F-23 Multi-Speed Preset 1 (Hz) Min speed -
Max speed
0.10 20
F-24 Multi-Speed Preset 2 (Hz) Min speed -
Max speed
0.10 20
F-25 Multi-Speed Preset 3 (Hz) Min speed -
Max speed
0.10 20