SP200 AC Drive Quick Start Guide
P-12 Configurable Output 0 0 = no fault x x x
1 = no fault/auto restarting x x x
2 = run x x x
3 = at frequency x x x
4 = above frequency x x x
5 = above current x x x
P-13Configurable Output Level 0.0 0 - 999.9 (only when P-12 = 4 or 5) x x x
Group 2: Speed Reference
P-20 Main Speed Reference 0 0 = analog input 1
0 = preset speeds
1 = keypad
2 = Internal / Jog Frequency (P-40)
3 = analog input 2
4 = Process Operation (P-29)
output
x
x
x
x
x
x
x
x
x
x
x
P-21Alternate Speed Reference 1 0 = analog input 1
0 = preset speeds
1 = keypad
2 = Internal / Jog Frequency (P-40)
3 = analog input 2
x
x
x
x
x
x
x
x
x
x
P-22 Analog Input 1 Offset 0.0 % 0 - 110.0 x x
P-23Analog Input 1 Gain 100.0 % 0 - 110.0 x x
P-24 Analog Input 2 Offset 0.0 % 0 - 110.0 x
P-25Analog Input 2 Gain 100.0 % 0 - 110.0 x
P-26 Process Proportional Gain 0.00 0 - 10.0 (0 = off) x
P-27Process Integral Gain 0.00 0 - 10.0 (0 = off) x
P-28 Process Reference 0 0 = analog input 1
1 = keypad
2 = Internal / Jog Frequency (P-40)
x
x
x
P-29Process Operation 0 0 = add Process Ref (P-28) and
analog input 2
1 = multiply Process Ref (P-28)
and analog input 2
2 = PI control
3 = inverted PI control
x
x
x
x
Group 3: Dynamic Control
P-30 Acceleration Time 1 5.0 sec 0 - 600.0 x x x
P-31
Deceleration Time 1 5.0 sec 0 - 600.0 x x x
P-32 Acceleration Time 2 10.0 sec 0 - 600.0 x x x
P-33
Deceleration Time 2 10.0 sec 0 - 600.0 x x x
P-34 Stop Control 0 0 = ramp-to-rest
1 = coast-to-rest
2 = DC injection
x
x
x
x
x
x
x
x
x
P-35
DC Brake Current 50 % 10 - 150 x x x
P-36 DC Brake Time at Stop 0.5 sec 0 - 20.0 x x x
Program Parameters
(Parameters that can be programmed only while the drive
is stopped are indicated by an asterisk *)
Units / Model
No. Name Default Range A B C