Quick Start Guide Manual

Drive Parameters
11
Drive Parameters
Display Parameters
(Read Only)
Units / Model
No. Name Default Range A B C
d-00 Command Frequency 0.1 Hz 0 - 240.0 x x x
d-01 Output Frequency 0.1 Hz 0 - 240.0 x x x
d-02 Output Current 0.1 A 0 - 200 (% of rated current) x x x
d-03 Bus Voltage 1 V 0 - 1000 x x x
d-04 Fault Code Annn alphanumeric code x x x
d-05 Input Status decimal 0000 - 7111 x x x
d-06 Drive Rating decimal x x x
d-07 Firmware Version Annn alphanumeric code x x x
d-08 Analog Input 1 Units 0.1 % 0 - 110.0 x x
d-09 Analog Input 2 Units 0.1 % 0 - 110.0 x
Program Parameters
(Parameters that can be programmed only while the drive
is stopped are indicated by an asterisk *)
Units / Model
No. Name Default Range A B C
Group 0: Protection
P-00 Minimum Speed * 0 Hz 0 - Maximum Speed x x x
P-01Maximum Speed * 60 Hz Minimum Speed - 240 x x x
P-02 Motor Overload Current x.x A 20% - 200% of drive’s rated current x x x
P-03Reverse Disable * 0 0 = reverse enabled
1 = reverse disabled
x x x
P-04 Auto Restart Attempts 0 0 - 10 x x x
P-05Current Limit 150 % 10% - 150% of drive’s rated current x x x
Group 1: Digital Input / Output
P-10 Start Control * 2 1 = keypad control
2 = 2-wire control
3 = 3-wire control
x
x
x
x
x
x
x
x
x
P-11Configurable Input * 2 (A) 0 = function loss (P-10 3) x
1 (B) 1 = disabled x
0 (C) 1 = preset x
1 = reverse run (2-wire) x
2 = jog (P-10
1)
x x
2 = jog (P-10
1 or 3)
x
3 = alternate spd ref select x x
3 = alt spd ref select (P-10 3) x
4 = n.c. coast-to-stop x x
4 = n.c. coast-to-stop (P-10
3)
x
5 = secondary accel/decel x x
5 = sec accel/decel (P-10
3)
x