Quick Start Guide Manual

Wiring AC Power and Control Terminals
5
Power Terminal Information
The terminal blocks accept up to 4 mm
2
(12 AWG) wire.
The recommended tightening torque is 1.35 Nm (12 in-lb).
Control Terminal Information
The terminal block is isolated from input power.
Control wires should be shielded and routed separately from the power wires.
The terminal block accepts 0.14 mm
2
(26 AWG) to 1.5 mm
2
(16 AWG) wire.
The maximum control wire length is 30 meters (100 ft).