Manual

7-22
Installing and Operating the SP200 AC Drive
d-05 Input Status
This parameter displays the status of
the inputs that are connected to the
control signal terminal block.
Parameter Range: 0000 to 7111
Running Access: RO
Left Digit
Value
Terminal 8
(Configurable Input)
Terminal 7
(Preset 2)
Terminal 6
(Preset 1)
0 OFF OFF OFF
1 OFF OFF ON
2 OFF ON OFF
3 OFF ON ON
4 ON OFF OFF
5 ON OFF ON
6 ON ON OFF
7 ON ON ON
Digit = 1 if the Function Loss/Reset Input (#3) is ON
Digit = 1 if the Forward Run Input (#4) is ON
Digit = 1 if the Reverse Run Input (#5) is ON
Digit = 1 if the Configurable Input (#6) is ON
F
or Model A (Single Channel Analog), the value is formatted as follows:
Digit = 1 if the Function Loss/Reset Input (#3) is ON
Digit = 1 if the Forward Run Input (#4) is ON
Digit = 1 if the Reverse Run Input (#5) is ON
This digit represents the combination of the Preset 1, Preset 2, and Configurable Inputs as
For Model B (Preset), the value is formatted as follows:
shown in the following table:
Digit = 1 if the Configurable Input (#3) is ON
Digit = 1 if the Forward Run Input (#4) is ON
Always 0
Always 0
F
or Model C (Dual Channel Analog), the value is formatted as follows: