Manual

7-18
Installing and Operating the SP200 AC Drive
P-51 Base Frequency Model
A B C
Use this parameter to set the motor
rated nameplate frequency.
Parameter Range: 0 to 240 (Hz) X X X
Default Setting: 60 X X X
Running Access: RW
P-52 Breakpoint Voltage Model
A B C
Use this parameter to define the
voltage corresponding to
P-53 (Breakpoint Frequency) for a
breakpoint in the V/Hz curve.
Parameter Range: 0 to rated drive voltage (V) X X X
Default Setting: 0 X X X
Running Access: RW
P-53 Breakpoint Frequency Model
A B C
Use this parameter to define the
frequency corresponding to
P-52 (Breakpoint Voltage) for a
breakpoint in the V/Hz curve.
Parameter Range: 0 to 240 (Hz) X X X
Default Setting: 0 (breakpoint disabled) X X X
Running Access: RW
P-54 Boost Voltage Model
A B C
Use this parameter to define the
amount of voltage applied to the
motor when running at 0 Hz.
Parameter Range: 0 to 20% of rated drive voltage (V) X X X
Default Setting: 5% of rated drive voltage X X X
Running Access: RW