Installing and Operating the SP200 AC Drive
P-35 DC Brake Current Model
A B C
Use this parameter to specify the
output current level that is applied to
the motor during DC injection braking.
Important: DC injection braking can
cause motor thermal failure if used
improperly or excessively.
Parameter Range: 10 to 150 (%) X X X
Default Setting: 50 X X X
Running Access: RW
P-36 DC Brake Time at Stop Model
A B C
Use this parameter to specify the time
that DC injection braking at the level
specified in P-35 (DC Brake Current)
will be applied to the motor. If P-34
Parameter Range: 0 to 20.0 (x.x seconds) X X X
Default Setting: 0.5 X X X
Running Access: RW
(Stop Control) is set to 0 to select ramp- to- stop, DC injection braking begins after the drive is stopped and the output
frequency has ramped down to zero. If P-34 (Stop Mode) is set to 2 to select DC injection braking, it begins immediately
when the drive is commanded to stop.
P-37 Avoidance Frequency Model
A B C
Use this parameter, along with P-38
(Avoidance Frequency Band), to
prevent the drive from continuous
operation within a range (band) of
Parameter Range: 0 to 240.0 (x.x Hz) X X X
Default Setting: 0 (disabled) X X X
Running Access: RW
frequencies. This may be useful to prevent continuous operation at undesirable speeds. This parameter
specifies the midpoint of the frequency avoidance band specified by P-38 (Avoidance Frequency Band). A
zero value disables this function.