Instruction Manual

A-10
SP120 AC Drive Installation and Operation
English
Line Filter Module Specifications
Current: at 40 °C ambient temperature
Overload: 150% IN for 10 min
Frequency: 50/60 Hz
Material: steel, surface refined
Humidity class: C
Operation height: < 1000 m without derating
> 1000 m, I
N
-2%, for each 1000m
Temperature range: -25 °C to +85 °C
Connections: Input terminals IP 20 and PE-screw M5
Load side: cable, unshielded
Line Filter
Module
Nominal
Voltage
(V)
Nominal
Current at
40
°C (A)
Leakage
Current at
50 Hz
(mA)
Test voltage
(VDC for 2 sec)
ph./ph.;
ph./ground
Input wire max.
cross section
(mm
2
)
L/N
Output cable
cross section
(mm
2
)
Heat
dissipation
(W)
S12-MF1-1010 100-120 10 < 3.5 N/A 4/4 3x1.5 N/A
S12-MF1-1016 100-120 16 < 3.5 N/A 4/4 3x1.5 N/A
S12-MF1-Y007 200-240 7 < 3.5 1400 / 2800 4/4 3x1.5 6
S12-MF1-Y012 200-240 12 < 3.5 1400 / 2800 4/4 3x1.5 7
S12-MF1-Y022 200-240 22 < 10 1400 / 1400 4/4 3x2.5 9
S12-MF1-2004 200-240 4 < 3.5 1400 / 2800 4/4 4x1.5 N/A
S12-MF1-2007 200-240 7 < 3.5 1400 / 2800 4/4 4x1.5 N/A
S12-MF1-2020 200-240 20 < 3.5 1400 / 1400 4/4 4x2.5 N/A
S12-MF1-4007 380-460 7 < 3.5 1978 / 2800 4/4 4x1.5 7
S12-MF1-4011 380-460 11 < 3.5 1978 / 2800 4/4 4x2.5 10
0
0,2
0,4
0,6
0,8
1,0
20 40 60 80 100
Temperature in °C
0
I
B
I
N
1,2