Instruction Manual
Parameters and Programming
3-21
English
Parameter
Number Parameter Name/Description
Min./Max
Range Units
Factory
Default
Communications
C70 Communication Command Select
Selects the source of the communication command.
Settings: 02 = Remote Operator
03 = RS422
02 to 03 Numeric
Value
02
C71 Baud Rate
Selects the Baud Rate for RS422 communication.
Settings: 04 = 4800 bps
05 = 9600 bps
06 = 19200 bps
04 to 06 Numeric
Value
04
C72 Drive Address
Sets the drive node address on the RS422 network.
01 to 32 N/A 01
C79 Communication Error Select
Selects the drives operation when a communication
error (E60) occurs.
Settings: 00 = Fault
01 = No Fault and continue operation
00 to 01 Numeric
Value
00
C91 Debug Mode
Used by Rockwell Automation field service personnel.
00 to 01 Numeric
Value
00
C92 - C95 [Reserved]
Reserved for future use. Do not change.
00 to 01 Numeric
Value
00
!
ATTENTION:If C91 [DEBUG MODE] is set
to 01, parameters C92 to C95 are
enabled. Do not change parameters C91
to C95. Failure to observe this precaution
could result in personal injury