Specifications

Publication 1747-SG001E-EN-E - February 2013
Select Network Communications 53
provides enterprise-wide systems access to plant-floor data. With an Ethernet network,
you can maximize communication between a wide variety of equipment.
Ethernet connectivity for SLC 500 is provided for the following:
SLC 5/05 processor
1761-NET-ENI/1761-NET-ENIW
MicroLogix 1000 controllers may be used with the 1761-NET-ENI, or -ENIW, however
some features are not supported:
Email (ENI/ENIW)
Controller store/download of device configuration (ENI/ENIW)
Floating point value display (ENIW)
Floating point value write from the device to the controller (ENIW)
Integer value write from the device to the controller (ENIW)
String file display (ENIW)
Ethernet Interface (ENI) and Web-Enabled Ethernet
Interface (ENIW)
The 1761-NET-ENI module provides EtherNet/IP Messaging connectivity for all DF1
full-duplex devices. The ENI allows users to easily connect SLC 5/03 and SLC 5/04
controllers onto new or existing Ethernet networks and upload/download programs,
communicate between controllers, and generate E-mail messages via SMTP (simple mail
transport protocol).
Compatible devices include: MicroLogix 1000/1200/1500, PLC-5, ControlLogix,
CompactLogix, and FlexLogix controllers, and computers running RSLinx.
The 1761-NET-ENIW module adds web-server capabilities, enabling the display of 4
standard data web pages with user-configurable data descriptions, and 10
userconfigurable web page links on the ENIW home page.
ETHERNET
FAULT
RS232
NET
TX/RX
TX/RX
PWR
CABLE
EXTERNAL
IP
SLC 5/05 Controller
Ethernet
Hub/Switch
MicroLogix 1500 Controller
1761-NET-ENI
Module
PC Ethernet
Interface Card
PC with
RSLogix 500
and RSLinx