Specifications

Chapter 3
Publication
1747-6.2
System Installation
Recommendations
To help you install the SLC 500 programmable controller as safely
and securely as possible, we have set up a few specific
recommendations for you to follow. For general installation
guidelines, also refer to the requirements specific to your region.
Europe: Reference the standards found in EN 60204 and your
national regulations.
United States: Refer to article 70E of the National Fire
Protection Association (NFPA). It describes electrical safety
requirements for employee workplaces.
This chapter covers the following:
typical installation
spacing your controllers
preventing excessive heat
grounding guidelines
master control relay
power considerations
safety considerations
preventive maintenance
The figure below consists of some components that make up a
typical installation. The following symbols are used:
NEMA rated enclosure suitable for your
application and environment that shields
your controller from electrical noise and
airborne contaminants.
Disconnect, to remove power from the system
Fused isolation transformer or a constant
voltage transformer, as your application
requires
Disconnect
Device
Isolation
Transformer
SLC 500
Controller
MCR
Master control relay/emergency-stop circuit
Terminal blocks or wiring ducts
Suppression devices for limiting EMI
(electromagnetic interference) generation
T
ypical
Installation