If there is high frequency conducted noise in or around your
distribution equipment, we recommend the use of an isolation
transformer in the AC line to the power supply. This type of
transformer provides isolation from your power distribution system
and is often used as a “step down” transformer to reduce line
voltage. Any transformer used with the controller must have a
sufficient power rating for its load. This power rating is generally
expressed in voltamperes (VA).
To select an appropriate isolation transformer, you must calculate the
power required by the chassis power supply (or supplies if more than
one chassis in system) and any input circuits and output loads that
are connected through this transformer.
You can find the power requirement (VA rating) for the chassis
power supplies in the specifications on page 2–11. The power
requirement for the input circuits is determined by the number of
inputs, the operating voltage, and the nominal input current. The
power requirement for output loads is determined by the number of
outputs, the load voltage, and load current.
For example, if you have a 1746-P1 power supply, 1746-IA16
16-point AC input module (12 mA at 120V ac) and a 1746-OA16
16-point AC triac output module (0.5A at 120V ac), the power
consumed would be:
135
V
A + (16)(120V)(0.012A) + (16)(120V)(0.5A) = 1,1
18 V
A
Important: In this case, 0.5A is the maximum rating of the triac
output (at 30° C). If your load draws less than 0.5A this
figure may be reduced accordingly. The output portion
of the VA calculation should reflect the current
requirements of your loads.
In general, we recommend that the transformer is oversized to
provide some margin for line voltage variations and other factors.
Typically a transformer that is 25% larger than the calculated VA is
sufficient.
Most industrial environments are susceptible to power transients or
spikes. To help insure fault free operation and protection of
equipment, we recommend suppression devices on power to the
equipment in addition to the isolation equipment.
S
electin
g
Isolation
Transformers