Specifications

2–1
1Selecting Your Hardware Components
Publication
1747-6.2
To select a power supply, you need the following documents:
power supply worksheet (see appendix E) one for each chassis
SLC 500 Family of Small Programmable Controllers System
Overview, publication 1747-2.30, or SLC 500 Modular Chassis
and Power Supplies Product Data, publication 1746-2.38.
When configuring a modular system, you must have a power supply
for each chassis. Careful system configuration will result in the best
performance. Excessive loading of the power supply outputs can
cause a power supply shutdown or premature failure.
There are three different AC power supplies and two DC power
supplies. For AC power supplies, the 120/240V selection is made by
a jumper. Place the jumper to match the input voltage. The power
supply has an LED that illuminates when the power supply is
functioning properly. Below are the general specifications for the
power supplies.
Power Supply Specifications
Description 1746-P1 1746-P2 1746-P3 1746-P4 1746-P5
Line
V
oltage
85-132/170-265V ac
47-63 Hz
85-132/170-265V ac
47-63 Hz
19.2-28.8V dc
85-132/170-265V ac
47-63 Hz
90–146V dc
T
ypical Line Power
Requirement
135 V
A
180 V
A
90 V
A
240 V
A
85 V
A
Maximum Inrush Current
20A 20A 20A 45A 20A
Internal Current Capacity
2A at 5V dc
0.46A at 24V dc
5A at 5V dc
0.96A at 24V dc
3.6A at 5V dc
0.87A at 24V dc
10.0A at 5V dc
2.88A at 24V dc
5.0A at 5V dc
0.96A at 24V dc
Fuse Protection
1746-F1 or equivalent:
250V
-3A Fuse
Nagasawa
ULCS-61ML-3
or BUSSMANN AGC 3
1746-F2 or equivalent:
250V
-3A Fuse
SANO SOC SD4 or
BUSSMANN AGC 3
1746-F3 or equivalent:
125V
-5A Fuse
Nagasawa
ULCS-61ML-5
or BUSSMAN AGC 5
Non-replaceable fuse
is soldered in place.
Non-replaceable fuse
is soldered in place.
24V dc User Power
Current Capacity
200 mA 200 mA
Not Applicable
1A
200 mA
24V dc User Power
V
oltage Range
18-30V dc 18-30V dc
Not Applicable
20.4-27.6V dc
18–30V dc
Operating T
emperature
0°
C to +60
°
C (+32
°F to +140°
F) Current capacity derated 5% above +55
°C.
0°
C to +60
°
C (+32
°F
to +140
°
F) no derating
0°
C to +60
°
C (+32
°F
to +140
°
F) Current
capacity derated 5%
above +55
°C.
Storage T
emperature
–40°
C to +85
°
C (–40
°F to +185°F)
Humidity Rating
5-95% (non-condensing)
Wiring
two #14 A
WG wires per terminal (maximum)
Certification
UL listed, CSA certified, CE compliant for all applicable directives, Class I Division 2 Hazardous Environment Certification
Refer to appendix F to determine line power requirements for your configuration.
Fuse is intended to guard against fire hazard due to short circuit conditions and may not protect the supply from damage under overload conditions.
The combination of all output power (5 volt backplane, 24 volt backplane, and 24 volt user source) cannot exceed 70 W
atts.
S
electin
g
Po
w
er
S
upplies