Specifications
2–7
Selecting Your Hardware Components
Publication
1747-6.2
DF1 Half-Duplex Protocol (Master and Slave) — DF1
Half-Duplex protocol provides a multi-drop single master/multiple
slave network capable of supporting up to 255 devices (nodes). This
protocol also provides modem support and is ideal for SCADA
(Supervisory Control and Data Acquisition) applications because of
the network capability.
ASCII Protocol — The ASCII protocol provides connection to other
ASCII devices, such as bar code readers, weigh scales, serial
printers, and other intelligent devices.
The following table summarizes the communication options for the
SLC 500 processor family.
Communications
Protocol
Processor
C
ommunications
Protocol
SLC 5/01
SLC 5/02 SLC 5/03 SLC 5/04 SLC 5/05
DH485 peer-to-peer receive only
receive
and initiate
receive
and initiate
–– ––
DH485 via RS232 port –– ––
receive
and initiate
➀
receive
and initiate
➀
receive
and initiate
➀
DF1 via RS232 port
(full-duplex or
half-duplex master or
slave)
receive only
➁
receive only
➁
receive
and initiate
receive
and initiate
receive
and initiate
ASCII via RS232 port –– ––
receive
and initiate
receive
and initiate
receive
and initiate
Data Highway Plus
(DH+)
receive only
➂
receive only
➂
receive
and initiate
➃
receive
and initiate
receive
and initiate
➃
Ethernet –– –– –– ––
receive
and initiate
➀
If
using 1747-AIC for isolation, connect to DH-485 network using 1747-PIC, if using 1761-NET-AIC for isolation, directly connect to DH-485 network with
1747-CP3 serial cable (or equivalent RS-232 null-modem cable).
➁
A 1747-KE or 1770-KF3 is required to bridge from DF1 (full-duplex or half-duplex slave only) to DH485.
➂
A 1785-KA5 is required to bridge from DH+ to DH485.
➃
Either a 1785-KA5 is required to bridge from DH+ to DH485 or the SLC-5/04’
s channel-to-channel passthru feature may be used to bridge between DH+ and
DH485 or between DH+ and DF1 Full-Duplex (DH+ -to- DF1 Full-Duplex passthru available starting with OS401). Another option is to use the 1785-KE to bridge
between DH+ and DF1 Full-Duplex or DH+ and a DF1 Half-Duplex Master/Slave network.
Note: The 1785-KA5 and 1785-KE modules require use of a 1771-series chassis and power supply.