Specifications
1–6
Quick Start for Experienced Users
Publication
1747-6.2
7. Load your software.
Reference
Refer to your software package’s documentation. –
8. Establish
communications to the processor
.
Reference
Follow the steps below:
1. Refer to the following to establish communications between the processor and your personal
computer.
Chapter 8
(Starting Up Your
Control System)
P
r
oc
ess
o
r:
P
r
oc
ed
u
re:
SLC 5/01 Connect 1747-PIC from the processor to your personal computer.
SLC 5/02 Connect 1747-PIC from the processor to your personal computer.
SLC 5/03 Connect 1747-PIC from the processor to your personal computer or a 1747-CP3 cable from
channel 0 of the processor to the personal computer serial port.
SLC 5/04 Connect a 1747-CP3 cable from channel 0 of the processor to the personal computer serial port
or use a KT, KTX, KT2, or PCMK card.
SLC 5/05 Connect a 1747-CP3 cable from channel 0 of the processor to the personal computer serial port.
For Ethernet connection, connect channel 1 of the processor and the PC Ethernet Card to an
Ethernet hub using 10Base-T cable.
2. Set the communication parameters of software to match the default parameters of the processor:
• SLC 5/01, SLC 5/02, and SLC 5/03 channel 1
DH-485
19.2K baud
Node Address = 1
• SLC 5/03 and SLC 5/04 only:
channel 0 configuration:
DF1 Full Duplex
No Handshaking
1200 baud
CRC Error Check
Duplicate Packet Detect On
No Parity
1 Stop Bit
• SLC 5/04 only:
channel 1 configuration:
DH+
57.6K baud
Node Address = 1
• SLC 5/05 only:
channel 0 configuration:
DF1 Full Duplex:
No Handshaking
19.2K baud
CRC Error Check
Duplicate Packet Detect On
No Parity
1 Stop Bit
channel 1 configuration:
Driver: Ethernet
➀
➀
Configuring
with BOOTP enabled so that a BOOTP server on the network can automatically provide the SLC 5/05 with the
configuration necessary to start communicating over Ethernet. See Appendix G for more information.