Specifications
10–16
Troubleshooting
Publication
1747-6.2
The Following
Error Exists
Probable Cause Recommended Action
System does
not operate per
programmed
forces.
User programmed
forces are not
enabled.
1. Monitor program file online and identify programmed
forces.
2. Enable appropriate forces and test system conditions
again. Once forces are enabled, the FORCE LED goes on
steady.
Refer to your programming software user manual.
The Following
Error Exists
Probable Cause Recommended Action
CPU Major
Error with Low
or No Battery
Back-up
Loss of RAM
during Power
Down Period
1. Verify battery is connected. See pages 6–1 and 9–5.
2. Replace the battery if you want RAM battery backup.
See page 9–5.
3. Refer to processor major fault recommended action
steps.
Refer to your programming software user manual.