Specifications

Chapter 9
Publication
1747-6.2
Maintaining Your Control
System
This chapter covers the following maintenance issues:
handling and storing battery, Catalog Number 1747-BA
installing and replacing the battery of the SLC 5/01 or SLC 5/02
processor
replacing your SLC 5/03, SLC 5/04, and SLC 5/05 battery
replacing retainer clips on an I/O module
replacing a fuse on the power supply
See page 3–12 for important information on testing the Master
Control Relay Circuit and Preventive Maintenance.
Follow the procedure below to ensure proper battery operation and
reduce personnel hazards.
Handling
Use only for the intended operation.
Do not ship or dispose of cells except according to recommended
procedures.
Do not ship on passenger aircraft.
!
ATTENTION: Do not charge the batteries. An
explosion could result or the cells could overheat
causing burns.
Do not open, puncture, crush, or otherwise mutilate the
batteries. A possibility of an explosion exists and/or
toxic, corrosive, and flammable liquids would be
exposed.
Do not incinerate or expose the batteries to high
temperatures. Do not attempt to solder batteries. An
explosion could result.
Do not short positive and negative terminals together.
Excessive heat can build up and cause severe burns.
Storing
Store the lithium batteries in a cool, dry environment, typically
+20° C to +25° C (+68° F to +77° F) and 40% to 60% relative
humidity. Store the batteries and a copy of the battery instruction
sheet in the original container, away from flammable materials.
Handling and Storing
Battery, Catalog Number