Specifications

36 SLC 500 Digital I/O Modules
Publication 1746-IN027D-EN-P - December 2012
AC Output Modules
Specifications – 1746-IH16
Attribute Value
(1)(2)(3)
Voltage category 125V DC signal input (sinking)
Number of inputs 16
Points per common 16
Voltage, operating Range:
90...146V DC
Points ON Simultaneously, max:
6 @ 146V DC and 30 °C (86 °F)
12 @ 146V DC and 50 °C (122 °F)
14 @ 132V DC and 55 °C (131 °F)
16 @ 125V DC and 60 °C (140 °F)
Backplane current
consumption
5V DC 0.085 A
24V DC 0.0 A
Signal delay, max On = 9 ms
Off = 9 ms
Off-state voltage, max 20.0V DC
Off-state current, max 0.8 mA
Input current, nom 2.15 mA @ 125V DC
2.25 mA @ 132V DC
(1)
Removable terminal block.
(2)
Use ID Code 0507 when configuring your system with programming software or the HHT.
(3)
If the input module is connected in parallel with an inductive load, use surge suppression across the load to protect
the input module from damage caused by reverse voltage. Refer to the SLC 500 Modular Hardware Style User
Manual, publication 1747-UM011, for more information on surge suppression.
Specifications – 1746-OA8, 1746-OA16, and 1746-OAP12
Attribute Value
1746-OA8 1746-OA16
(5)
1746-OAP12
(5)(6)(7)
Voltage category 120/240V AC signal input
Number of outputs 8 16 12
Points per common 4 8 6
Voltage, operating 85...265V AC @ 47...63 Hz
Backplane current
consumption
5V DC 0.185 A 0.370 A 0.370 A
24V DC
Signal delay, max resistive load
(1)
On = 1 ms
Off = 11.0 ms
Off-state leakage, max
(2)