Manual

Rockwell Automation Publication 20L-IN015A-EN-P - February 2012 3
Filter Capacitor Replacement Kit SK-L1-CAP2-D650 for PowerFlex 700L Frame 3A 480V AC Drives
Tools That You Need
Properly-rated, isolated multi-meter (DMM) to measure the AC input
and DC filter capacitor voltages (working voltage specifications should be
1000V)
3/8-inch drive ratchet
3/8-inch drive 10 mm deep well socket
3/8-inch drive 3/4-inch deep well socket
Torque wrench capable of 50 lb•in (5.6 N•m)
Torque wrench capable of 35 lb•ft (47.5 N•m)
10 mm box wrench
#1 Phillips screwdriver
Small wire cutter
Lockout/Tagout kit
Work g loves
Arc Flash Gear
You may also need a box or container to hold loose hardware.
Precheck
Drives built prior to May 2008 had older style SPDs mounted on the filter
capacitor bank assemblies. If a surge trap style SPD is not installed in the drive, it
is necessary to order and install a surge trap upgrade kit, Catalog Number 21T-
385253-A01 to insure there is proper transient protection for the equipment.
IMPORTANT
Inspect the surge trap (SPD) in the drive and note whether the visual
inspection tab has been activated. This indicates internal damage and the need
for replacement. For the location of the surge trap, see Figure 1 on page 5
.
Visual Inspection Tab DetailSurge Trap (SPD) in Drive