Owner manual
Trustedâ„¢ Bridge Module 8161
Issue 2 Feb 10 PD-8161 35
Word 4 Fault flags, 0=healthy 1=fault
bit 0-2 Logic supply power fail fault (ABC, bit0=A, bit2=C)
bit 3-5 Field supply power fail fault (ABC)
bit 6 Bias supply 1 power fail fault
bit 7 Bias supply 2 power fail fault
bit 8 Logic supply power fail fault
bit 9-10 Reserved
bit 11-13 Drive supply power fail fault (ABC)
bit 14 Field supply power fail fault
bit 15 Over temperature fault
RACK 3: (FAULTS)
2 INTEGER inputs
Word 1 LFD errors, channels 1-16 (bit 0 = channel 1)
Word 2 LFD errors, channels 17-32 (bit 0 = channel 17)