Owner manual

Trustedâ„¢ Bridge Module 8161
Issue 2 Feb 10 PD-8161 32
3.2.13 Module – mdo16gns (48v; digital output Module)
DESCRIPTION
T
his definition will open a single MDO16GNS.
OEM PARAMETERS
OEM parameter Valid numbers Description
CHASSIS 2-29 Logical chassis and slot number where the
SLOT 1-10 MDO16GNS is located.
PHYSICAL MODULE:
RACK 1: (DO)
16 BOOLEAN outputs
RACK 2: (DIAG)
4 INTEGER inputs
Word 1 Health status bits, 0=healthy 1=fault
bit 0-2 Microcontroller watchdog (bit 0=A, bit 1=B, bit2=C)
bit 3-5 MP watchdog (bit 0=A, bit 1=B, bit2=C)
bit 6-8 Microcontroller slice health (bit 0=A, bit 1=B, bit2=C)
bit 9-11 Combined slice health (bit 0=A, bit 1=B, bit2=C)
bit 12 Power Fail
bit 13-15 not used
Word 2 Diagnostic bits
bit 0 Slice A
=1 slice is not responding or there is an error
=0 slice is responding
bit 1 Slice B
=1 slice is not responding or there is an error
=0 slice is responding
bit 2 Slice C
=1 slice is not responding or there is an error
=0 slice is responding
bit 3 Module offline or missing
=1 offline or missing
=0 online
bit 4 Single slot hot repair
=1 in progress
=0 not in progress
bit 5 Discrepancy errors
=1 faults detected
=0 no faults detected
bit 6 LFD faults
=1 faults detected
=0 no faults detected
Word 3 Slot number of active module