,Startup,Guide User Manual
PMI Regulator Operating Modes
3-1
CHAPTER 3
PMI Regulator Operating Modes
The PMI Regulator’s default operating mode is idle. All other operating modes are
selected by the programmer in the Drive Control register (100/1100). Table 3.1 shows
the available operating modes. Note that the operating modes are mutually exclusive,
i.e., only one mode may be enabled at a time (this is checked by the interlock tests).
The PMI Regulator’s operating modes are shown in figure 3.1 and are described in the
following sections.
Table 3.1 – PMI Regulator Operating Modes
Operating
Mode
Drive Control
Register Bit Mode Description
Idle N/A The PMI Regulator’s default operating mode during which no
algorithms are running.
Enable PMI Run 0 Executes the control algorithms.
Enable Tuning 1 Calculates gain values for the control algorithm.
Bridge Test
Enable
2 Performs a test to verify gate cable connections and power
devices.