User guide
Technical Specifications
A-7
575 VAC Output Drives
C/W 001 2.5
4444
C/W 003 6
4444
C/W 007 10
4
91 217 308
C/W 010 12
4
103 251 354
C/W 015 19
4
117 360 477
C/W 020 24
4
140 467 607
C/W 025 30
4
141 492 633
C/W 030 35
4
141 526 667
C/W 040 45
4
175 678 853
C/W 050 57
4
193 899 1092
C/W 060 62
4
193 981 1174
C/W 075 87 Fig A.18 361 1553 1894
C/W 100 109 Fig A.19 426 1978 2504
C/W 125 138 Fig A.20 522 2162 2683
C/W 150 160 Fig A.21
444
C/W 200 252 Fig A.22 755 3065 3820
C/W 250 284 Fig A.23 890 3625 4515
C/W 300
5
298 None 926 5015 5941
C/W 350
5
354 None 1000 5935 6935
C/W 400
5
406 Fig A.24 1430 7120 8550
C/W 450
5
460 Fig A.25 1465 8020 9485
C/W 500
5
505 Fig A.26 1500 8925 10425
C/W 600
5
600 Fig A.27 1610 10767 12377
C/W 650
5
673 Fig A.28 1700 12000 14000
W 800 800 None
1. Base Amps with nominal input voltage (240, 480, or 600V). If input voltage exceeds rating, drive output
must be derated. Refer to figure A.30.
2. Drive ambient temperature rating is 40° C. If ambient temperature exceeds 40° C, the drive must be
derated. Refer to figures A.1 to A.28.
3. Drive rating is based on altitudes of 100 m (3300 ft) or less. If installed at a higher altitude, drive must be
derated. Refer to figure A.29.
4. Not available at time of publication.
5. Important: Two (2) 725 CFM fans are required if an open type drive is mounted in a user-supplied
enclosure.
Table A.2 – Enclosure Requirements
Power
Module
Model No.
Base
Derate
Amps
1
Derating
Curve
2,3
Heat
Dissipation
Watts
2,3
Heatsink
Watts
2
Total
Watts
2