User guide

Technical Specifications
A-3
Overload Capability
Continuous: 100% Fundamental current
1 minute: 150% (B - G frame Power Modules)
135% (H frame Power Modules)
Output Frequency Range
Vector Mode: 0 - 400 Hz (limited by feedback devices)
V/Hz Mode: 0 - 600 Hz
Output Waveform
Sinusoidal (PWM)
Maximum Short Circuit Current Rating
200,000 A rms symmetrical, 600 volts (when used with AC input line fuses
specified in table 3.2).
Ride Through
2 seconds minimum
Efficiency
97.5% at rated amps, nominal line volts
Ground Fault Trip Threshold
Power Module
Model Numbers Trip Level
A001 - A003
Q 001 - Q 003
B 001 - B 003
R 001 - R 003
C 001 - C 003
W 001 - W 003
20A
A 007 - A 125
Q 007 - Q 125
B 007 - B 600
R 007 - R 800
C 007 - C 650
W 007 - W 800
100A