Ambient Conditions
• Operating Temperature: Open chassis: 0 to 50° C (32 to 122
°
F)
Enclosed chassis: 0 to 40
°
C (32 to 104
°
F).
• Storage Temperature: -40 to 70
°
C (-40 to 158
°
F).
• Relative Humidity: 5 - 95% non-condensing
• Altitude: 1000m (3300 ft) without derating
• Shock: 15g peak for 11 ms duration (+ 1.0 ms).
• Vibration: 0.0006 inches (0.152 mm) displacement. 1G peak.
Input Voltage Rating
• 200 - 240 VAC, Standalone, 3 Phase, +/-10%, nominal
• 380 - 480 VAC, Standalone, 3 Phase, +/-10%, nominal
• 500 - 600 VAC Standalone, 3 Phase, +/-10%, nominal
• 310 VDC, Common Bus, +/-10%, nominal
• 513 - 620 VDC, Common Bus, +/-10%, nominal
• 675 - 800 VDC, Common Bus, +/-10%, nominal
Input Power Rating
• 2 - 134 KVA (230V)
• 2 - 437 KVA (380V)
• 2 - 555 KVA (460V)
• 2/3 - 578/694 KVA (500/600V)
Input Frequency
• 50/60 Hz (+/-3 Hz)