Owner's manual
8-8
PROFIBUS Communications Module
8 Online @ 125k bps The module and DPI product are
communicating at 125 kbps.
9 Online @ 500 kbps The module and DPI product are
communicating at 500 kbps.
10 Bad Host Flt The module was connected to an incompatible
product.
11 Dup. Port Flt Another peripheral with the same port number
is already in use.
12 Type 0 Login The module has logged in for type 0 control.
13 Type 0 Time Flt The module has not received a type 0 status
message within the specified time.
14 DL Login The module has logged into a datalink.
15 DL Reject Flt The host rejected an attempt to log in to a
datalink because the datalink is not supported
or is used by another peripheral.
16 DL Time Flt The module has not received a datalink
message within the specified time.
17 Control Disabled The module has sent a “Soft Control Disable”
command to the DPI product.
18 Control Enabled The module has sent a “Soft Control Enable”
command to the DPI product.
19 Message Timeout A Client-Server message sent by the
peripheral was not completed.
20 DPI Fault Msg The Host faulted.
21 DPI Fault Clear The user cleared a fault in the module.
22 Normal Startup Peripheral completes a normal startup.
23 NET Comm Flt The module detected a fault condition on the
PROFIBUS network.
24 Fault Cfg Error One of the Flt Cfg data Parameters is set to a
value greater than 65535 and the host requires
a 16-bit value.
25 P-DP Online The PROFIBUS module has gone on-line the
PROFIBUS network.
26 P-DP Offline The PROFIBUS module has gone off-line the
PROFIBUS network.
27 P-DP Idle The PROFIBUS module received a network
clear from the PROFIBUS master.
28 Language CRC Bad The language flash segment is corrupt; flash
the module.
Table 8.5 – Event Codes and Descriptions
Code Event Description