Owner's manual

Configuring the PROFIBUS Scanner
5-17
Step 29. Station 1 is configured as follows:
Note that Station 1 occupies 14 words (0-13).
Step 30. The same steps for configuring Station 1 will be used for
configuring Station 2. Refer to previous steps (starting at
step 9,) for Configuring the SST-PFB-SLC PROFIBUS
Scanner-Station 2. (See figure 5.31.)
Station 2 is configured as follows:
Note that Station 2 occupies 14 words (14-27).
Step 31. Use the null modem cable that came with the scanner to
connect COM1 on the PC and the CONFIG RS232 port
on the scanner.
Module M1/M0 Word
Ctrl/Stat & Ref Fdbk 0
Datalink A 2
Datalink B 4
Datalink C 6
Datalink D 8
Parameter Access 10
Figure 5.31 – Station 2 Network Window
[001]_RECOMM_PBUS(**)
[002]_RECOMM_PBUS(**)
Module M1/M0 Offset
Ctrl/Stat & Ref Fdbk 14
Datalink A 16
Datalink B 18
Datalink C 20
Datalink D 22
Parameter Access 24