Owner's manual

PROFIBUS Module Parameters
B-7
Sets the Reference data that is sent to the drive if any of the
following is true:
Comm Flt Action (parameter 9) is set to Send Flt Cfg and
communications are disrupted.
Idle Flt Action (parameter 10) is set to Send Flt Cfg and the
scanner is put into Program mode.
Important: If the drive uses a 16-bit Reference, the most significant
word of this value must be set to zero (0) or a fault will
occur.
Sets the data that is sent to the Datalink in the drive if any of the
following is true:
Comm Flt Action (parameter 9) is set to Send Flt Cfg and
communications are disrupted.
Idle Flt Action (parameter 10) is set to Send Flt Cfg and the
scanner is put into Program mode.
14 Flt Cfg Ref
Range: 0 to 4294967295
Default: 0
Type: Read/Write
Reset Required: No
15
16
17
18
19
20
21
22
Flt Cfg A1
Flt Cfg A2
Flt Cfg B1
Flt Cfg B2
Flt Cfg C1
Flt Cfg C2
Flt Cfg D1
Flt Cfg D2
Range: 0 to 4294967295
Default: 0
Type: Read/Write
Reset Required: No