User guide

8-2
Interbus Communications Module
Important:
Interbus compliance requires different LED functions
than what is normally displayed on the front of the
drive (Port, Mod, Net A and Net B LEDs). LED labels
are provided with the module for application to the
drive cover.
8.2 Cable Check (CC) Status Indicator
8.3 Remote Bus Disable (RD) Status
Indicator
8.4 Transmit/Receive (TR) Status
Indicator
Table 8.1 – Cable Check (CC) Status Indicator: State Definitions
Status Cause Corrective Action
Off Master is reset or no
cable connection.
Connect the module to the
network using an Interbus
cable.
Verify master not in reset.
Solid
Green
Cable connection
good.
No action required.
Table 8.2 – Remote Bus Disable (RD) Status Indicator: State Definitions
Status Cause Corrective Action
Off Outgoing remote bus
is not switched off.
No action required.
Solid Red Outgoing remote bus
is switched off.
Read configuration or start data
transmission. Master may have
to be reset first.
Table 8.3 – Transmit/Receive (TR) Status Indicator: State Definitions
Status Cause Corrective Actions
Off No PCP connection is
carried out.
Verify that master is sending
PCP messages.
Solid
Green
A PCP connection is
being carried out.
Flashes when a new
PCP frame has been
received.
No action required.