User guide

Configuring the Interbus Scanner
5-17
Refer to the SST_IBS_SLC User’s Guide for more information.
Table 5.5 – G File Data Information
Word
Value
(Decimal)
Value
(Hexadecimal) Description
0 8224 2020 Fixed to 2020h by the SLC
1 4096 1000 Enables the command interface
between the SLC and the USC/4
2 0 0 Use the CMD specified Bus Update
Time
3 0 0 Use the CMD specified Bus Warning
Time
4 0 0 Use the CMD specified Bus Timeout
5 0 0 The number of words used at the
beginning of the M files for Inputs
and Outputs
6 128 80 Maximum data size for commands
and replies sent between the SLC
and the scanner