Owner's manual
8-2
EtherNet/IP Communications Module
8.1.1 DRIVE Status Indicator
Table 8.2 – DRIVE Status Indicator: State Definitions
Status Cause Corrective Action
Off The module is not
powered or is not
connected properly to
the drive.
• Securely connect the module
to the drive using the ribbon
cable.
• Apply power to the drive.
Flashing
Red
The module is not
receiving a ping
message from the
drive.
• Verify that cables are
securely connected.
• Cycle power to the drive.
Solid
Red
The drive has refused
an I/O connection from
the module.
Another DPI peripheral
is using the same DPI
port as the module.
Important: Cycle power to the
product after making any of the
following corrections:
• Verify that all DPI cables are
securely connected and not
damaged. Replace cables if
necessary.
• Verify that the DPI Host
supports Datalinks.
• Configure the module and
DPI Host to use a Datalink
that is not already being
used by another peripheral.
Orange The module is
connected to a product
that does not support
Reliance Electric DPI
communications.
• Connect the module to a
product that supports
Reliance Electric DPI
communications (for
example, SP600, LiquiFlo
2.0 or GV6000 drives).
Flashing
Green
The module is
establishing an I/O
connection to the drive.
• No action. Normal behavior if
no DPI I/O is enabled.
Solid
Green
The module is properly
connected and is
communicating with the
drive.
• No action.