Troubleshooting the ControlNet Module and Network
8-5
8.1.4 NET A and B Independently
Table 8.4 NET A and B Independently: State Definitions
Status Cause Corrective Actions
One
channel
LED is
steady off
That channel is
disabled or not
supported.
Program the network for
redundant media, if required.
One
channel
LED is
flashing
red/green
There is an invalid
link configuration
for that channel.
Power cycle or reset the
module.
Reset the controller.
If the problem persists, contact
Rockwell Automation support.
One
channel
LED is
flashing
red/off
The channel is not
receiving network
activity.
Check media for broken calbes,
loose connectors, missing
terminators, etc.
One
channel
LED is
flashing
green/off
A temporary
channel error has
occurred, or the
channel is in listen-
only mode.
Verify the controller is present
on the network and working.
One
channel
LED is
steady
green
Normal operation
for that channel.
No action required.