Owner manual

8-4
ControlNet Communications Module
8.1.3 NET A and B Together
Table 8.3 NET A and B Together: State Definitions
Status Cause Corrective Actions
Both LEDs
are off
A reset occurred or
there is no power.
Apply power to the module.
Both LEDs
are steady
red
A link interface
failed.
Check media for broken cables,
loose connectors, missing
terminators, etc.
Power cycle or reset the
module. If the problem persists,
contact Rockwell Automation
support.
LEDs are
alternating
red/green
The module is in
self-test mode.
No action required. The module
will exit this mode when the
self-test is completed.
LEDs are
alternating
red/off
There is a bad
configuration.
Verify that all node addresses
are unique.
Check the modules
configuration.
Check media for broken cables,
loose connectors, missing
terminators, etc.
Power cycle or reset the
module.