Owner manual

7-22
ControlNet Communications Module
(Destination) Response Data
A Set _Attributes_Scattered message is used to write multiple
parameters that may or may not be in sequential order (figure 7.26).
A Service Code of 4C indicates the Set_Attributes_Scattered
service (see page C-20, Object Specific Services).
0 12 Parameter Number = 12
1 3333 Value = 333.3VDC
2 0 (Pad Word)
3 11 Parameter Number = 11
4 0 Value = 0.0Hz
5 0 (Pad Word)
6 10 Parameter Number = 10
7 148 Value = 14.8Hrs
8
9 9 Parameter Number = 9
10 23 Value = 2.3MWh
11
Figure 7.26 Set_Attributes_Scattered Message Screen