ControlNet Communications Module
Step 15. Enter a file name and click
S
ave
. The project is now
saved for future use.
5.1.3 Verifying Network Properties
In the
N
etwork
menu, select
Properties
to display the ControlNet
dialog box (figure 5.26). Verify:
•
The number in the
Max S
cheduled Address
field is higher than
or equal to the highest node number that will perform I/O
messaging.
•
The number in the
Max U
nscheduled Address
field is higher
than or equal to the highest node number on the network.
•
The correct type of media redundancy is selected in the
M
edia
Redundancy
field.
Important:
The value in the
Network Update T
ime (ms)
field is
5 ms or greater. Do not set lower than 5 ms. The NUT
must be set equal or lower than the RPI times set for
the devices on the network.