Owner manual
4-8
ControlNet Communications Module
Set Reset Module (9) to Reset Module. See figure 4.7.
When you enter
1 (Reset Module)
, the module will be immediately
reset. When you enter
2 (Set Defaults)
, the module will set all
module parameters to their factory-default settings. The value of this
parameter will be restored to
0 (Ready)
after the module is reset or
resetting the defaults. The module should be reset after performing
a “Set Defaults.”
4.8 Viewing the Module Configuration
The parameters in table 4.4 provide information about how the
module is configured. You can view these parameters at any time.
Figure 4.7 – Reset Screen on an LCD OIM
Port 5 Device
RECOMM-CNET
Parameter #: 9
Reset Module
1
Reset Module
Value Description
0 Ready (Default)
1 Reset Module
2 Set Defaults
Table 4.4 – Module Configuration Status Parameters
No. Name and Description
Details
01
DPI Port
Port to which the module is connected. This will
usually be port 5.
Default: 5
Minimum: 0
Maximum: 7
Type: Read Only
02
DPI Data Rate
Data rate used by the drive. This data rate is set in
the drive and the module detects it.
Default: 0 = 125 K
Values 0 = 125 K
1 = 500 K
Type: Read Only
04
CN Addr Act
The actual network node address.
Default: 2
Minimum: 1
Maximum: 99
Type: Read Only
06
CN Rate Act
The actual network data rate.
Default: 0 = 5 Mbps
Values: 0 = 5 Mbps
Type: Read Only
07
Ref/Fdbk Size
Size of the Reference/Feedback. The drive
determines the size of the Reference/Feedback.
Default: 0 = 16-bit
Values: 0 = 16-bit
1 = 32-bit
Type: Read Only
08
Datalink Size
Size of each Datalink word. The drive determines
the size of Datalinks.
Default: 0 = 16-bit
Values: 0 = 16-bit
1 = 32-bit
Type: Read Only