Troubleshooting the ControlNet Module and Network
8-9
9 Online @ 500kbps The module and DPI product are
communicating at 500 kbps.
10 Bad Host Flt The module was connected to an incompatible
product.
11 Dup. Port Flt Another peripheral with the same port number
is already in use.
12 Type 0 Login The module has logged in for type 0 control.
13 Type 0 Time Flt The module has not received a type 0 status
message within the specified time.
14 DL Login The module has logged into a datalink.
15 DL Reject Flt The host rejected an attempt to log in to a
datalink because the datalink is not supported
or is used by another peripheral.
16 DL Time Flt The module has not received a datalink
message within the specified time.
17 Reserved Not used.
18 Control Disabled The module has sent a Soft Control Disable
command to the DPI product.
19 Control Enabled The module has sent a Soft Control Enable
command to the DPI product.
20 Message Timeout A Client-Server message sent by the
peripheral was not completed.
21 Flt Cfg Error Flt Cfg for the Reference or Data links is set to
a value greater than 65535 and the drive is set
for 16-bit.
22 App CRC Flt Start-up sequence detected corrupt
application firmware.
23 App Updated Start-up sequence detected new application
firmware in candidate area.
24 CN Comm Flt The module detected a fault condition on the
ControlNet network.
25 CN Sent Reset The peripheral received a reset from the
network.
26 CN Close Fit An I/O connection from the network to the
peripheral was closed.
27 CN Idle Flt The peripheral is receiving idle packets from
the network.
28 CN Open An I/O connection to the peripheral from the
network has been opened.
29 Net Timeout Flt An I/O connection from the network to the
peripheral has timed out.
30 PCCC IO Close The device sending PCCC Control messages
to the peripheral has sent the PCCC Control
Timeout to a value of zero.
Table 8.6 Event Codes and Descriptions