User guide
Troubleshooting the Module and Network
6-3
6.1.2 MS Status Indicator
Table 6.2 – MS Status Indicator: State Definitions
Status Cause Corrective Action
Off The module is not
powered.
• Securely connect the module
to the SP600 drive using the
Internal Interface cable.
• Apply power to the drive.
Flashing
Red
The module has
failed the firmware
test.
• Clear faults in the module.
• Cycle power to the drive.
• If cycling power does not
correct the problem, the
parameter settings may have
been corrupted. Reset defaults
and reconfigure the module.
• If resetting defaults does not
correct the problem, flash the
module with the latest firmware
release.
Solid
Red
The module has
failed the hardware
test.
• Cycle power to the drive.
• Replace the module.
Flashing
Green
The module is
operational but is not
transferring I/O data.
• Place the scanner in RUN
mode.
• Program the controller to
recognize and transmit I/O to
the module.
• Configure the module for the
program in the controller.
• Normal behavior if no DPI I/O
is enabled.
Solid
Green
The module is
operational and
transferring I/O data.
• No action required.