RS485 DF1 Communications Module M/N RECOMM-485 Instruction Manual D2-3514
The information in this manual is subject to change without notice. Throughout this manual, the following notes are used to alert you to safety considerations: ! ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Important: Identifies information that is critical for successful application and understanding of the product. ! ATTENTION: The drive may contain high voltages that can cause injury or death.
CONTENTS Chapter 1 Introduction 1.1 Module Features............................................................ 1-1 1.2 Related Documentation ................................................. 1-2 1.3 Getting Assistance from Reliance Electric..................... 1-2 Chapter 2 Getting Started 2.1 Required Equipment ...................................................... 2-2 2.2 Installation Checklist ...................................................... 2-3 Chapter 3 Installing the RS485 DF1 Module 3.
Appendix A Technical Specifications ...................................................... A-1 Appendix B RS485 DF1 Module Parameters .......................................... B-1 Appendix C Logic Command/Status Words............................................. C-1 Glossary ..................................................................................Glossary-1 Index .......................................................................................
List of Figures Figure 2.1 – Components of the RS485 DF1 Module................................. 2-1 Figure 3.1 – Setting the Module’s Node Address ....................................... 3-2 Figure 3.2 – Setting the Data Rate ............................................................. 3-2 Figure 3.3 – DPI Ports and Internal Interface Cables ................................. 3-4 Figure 3.4 – Mounting the Module .............................................................. 3-5 Figure 3.
IV RS485 DF1 Communications Module
List of Tables Table 2.1 – Equipment Shipped with the RS485 DF1 Module.................... 2-2 Table 2.2 – Required User-Supplied Equipment ........................................ 2-2 Table 4.1 – Configuration Tools.................................................................. 4-1 Table 4.2 – Selections for Drive Response to Communication Fault.......... 4-5 Table 4.3 – Fault Configuration Parameters ............................................... 4-6 Table 4.
VI RS485 DF1 Communications Module
CHAPTER 1 Introduction This manual provides information about the RS485 DF1 Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar with installing, programming, and maintaining AC drives and networks. The RS485 DF1 Communications module allows an RS485 DF1 Master device to access the SP600 drive using: • • • • Logic Command/Reference (Start, Stop, Reference, etc.
1.2 • A number of tools to configure the module and connected drive. These tools include the LCD OIM and VS Utilities software. • User-defined fault actions that determine how the module and the drive respond to communication disruptions on the network. Related Documentation Refer to the following related publications as necessary for more information. All of the publications are available from http://www.theautomationbookstore.com or http://www.reliance.com. 1.
CHAPTER 2 Getting Started This chapter provides: • • • • A description of the RS485 DF1 module’s components A list of parts shipped with the module A list of user-supplied parts required for installing the module An installation checklist Status Indicators Four LEDs to indicate the status of the connected drive, module, and network. Refer to chapter 6 for more information about the LEDs. DPI Connector A 20-pin, single-row shrouded male header.
2.1 Required Equipment Table 2.1 lists the equipment shipped with the RS485 DF1 module. When you unpack the module, verify that the package includes all of these items. Table 2.1 – Equipment Shipped with the RS485 DF1 Module Item Description One RS485 DF1 Communication Module One 2.54 cm (1 in) and one 15.
2.2 Installation Checklist This section is designed to help experienced users start using the RS485 DF1 module. If you are unsure how to complete a step, refer to the referenced chapter. ✔ Step ❒ 1 Review the safety precautions for the module. Throughout this manual ❒ 2 Verify that the drive is properly installed. SP600 AC Drive User Manual ❒ 3 Commission the module. Chapter 3 Action Refer to: Set a unique node address and the appropriate data rate using the switches on the module.
2-4 RS485 DF1 Communication Module
CHAPTER 3 Installing the RS485 DF1 Module Chapter 3 provides instructions for installing the module on an SP600 drive. 3.1 Preparing for an Installation Before installing the module, verify that you have all required equipment. Refer to chapter 2, Getting Started, for a list of equipment. 3.2 Commissioning the Module To commission the module, you must set a unique node address on the network, the data rate used by the network, and the errorchecking method.
2 2 3 4 1 0 5 9 Setting 00 to 99 4 0 6 8 3 1 5 9 7 6 8 7 Description The node address used by the module if switches are enabled. The default switch setting is 01. Important: If the Data Rate switch is set to “PGM” (Program), the module will use the setting of DF1 Addr Cfg (module parameter 3) for the node address. The default setting of this parameter is 1. Refer to chapter 4, Configuring the RS485 DF1 Module, for more information. Figure 3.1 – Setting the Module’s Node Address Step 2.
3.3 Connecting the Module to the Drive ATTENTION: The SP600 drive may contain high voltages that can cause injury or death. Remove power from the drive, and then verify power has been discharged before installing or removing a module. Failure to observe this precaution could result in severe bodily injury or loss of life. ! Step 1. Remove power from the drive. Step 2. Use static control precautions. Step 3.
RS485 DF1 Module SP600 Drive 1-20 HP SP600 Drive Frame 2 and Larger DPI Connector RS485 Connector 15.24 cm (6 in) Internal Interface cable 2.54 cm (1 in) Internal Interface cable Figure 3.
Drive Module Internal Interface cable folded behind the module and in front of the drive SP600 Drive 1-20 HP SP600 Drive Frame 2 and Larger Figure 3.
3.4 Connecting the Module to the Network ATTENTION: The SP600 drive may contain high voltages that can cause injury or death. Remove power from the drive, and then verify power has been discharged before installing or removing a module. Failure to observe this precaution could result in severe bodily injury or loss of life. ! Step 1. Remove power from the drive. Step 2. Use static control precautions. Step 3. Connect an RS485 cable to the network, and route it through the bottom of the drive.
3.5 Applying Power ! ATTENTION: Unpredictable operation may occur if parameter settings and switch settings are not compatible with your application. Verify that settings are compatible with your application before applying power to the drive. Failure to observe these precautions could result in severe bodily injury of loss of life. Step 1. Close the door or reinstall the cover on the drive. The status indicators can be viewed on the front of the drive after power has been applied. Step 2.
3-8 RS485 DF1 Communications Module
CHAPTER 4 Configuring the RS485 DF1 Module Chapter 4 provides instructions and information for setting the parameters in the module. For a complete list of parameters, refer to Appendix B, RS485 DF1 Module Parameters. For definitions of terms in this chapter, refer to the Glossary. 4.1 Configuration Tools The module stores parameters and other information in its own nonvolatile memory. Therefore, you must access the module to view and edit its parameters. Table 4.
4.2 Using the LCD OIM to Configure the Module Use the procedure in figure 4.1 to access the parameters on the RS485 DF1 module using the LCD OIM. If you are unfamiliar with the operation of the LCD OIM, refer to the SP600 AC Drive User Manual (D2-3485 or D2-3501) for more information.
4.4 Setting the Data Rate If the Data Rate switch on the module is set to “PGM,” the value of module parameter 5 (DF1 Rate Cfg) determines the RS485 DF1 data rate. Your application may require a different setting. Step 1. Set the value of module parameter 5 (DF1 Rate Cfg) to the data rate at which your network is operating. Refer to figure 4.3. Port 5 Device RECOMM-485 Parameter #: 5 DF1 Rate Cfg 3 9600 bps Value 0 1 2 3 4 5 Baud Rate 1200 bps 2400 bps 4800 bps 9600 bps (default) 19.2 kbps 38.
4.6 Setting the I/O Configuration The I/O configuration determines the type of data sent to the drive. This is a two-part process: enabling/disabling the data transmitted between the module and the drive, and identifying the data transmitted between the module and the master (i.e., scanner). Step 1. Enable or disable the data transmitted between the module and the drive by setting the bits in module parameter 12 (DPI I/O Config). A “1” enables the I/O. A “0” disables the I/O. Bit 0 is the right-most bit.
4.7 Setting a Fault Action By default, when communications are disrupted (for example, a cable is disconnected) or the scanner is idle, the drive responds by faulting if it is using I/O from the network. You can configure a different response to communication disruptions using module parameter 10 (Comm Flt Action). ! ATTENTION: Module parameter 10 (Comm Flt Action) lets you determine the action of the module and connected drive if communications are disrupted. By default, this parameter faults the drive.
4.7.1 Setting the Fault Configuration Parameters If you set module parameter 10 (Comm Flt Action) to “Send Flt Cfg,” the values in the parameters shown in table 4.3 are sent to the drive after a communications fault occurs. You must set these parameters to values required by your application. Table 4.3 – Fault Configuration Parameters Parameter Number Name Description 14 Flt Cfg Logic A 16-bit value sent to the drive for Logic Command.
Set module parameter 9 (Reset Module) to “Reset Module.” See figure 4.7. Port 5 Device RECOMM-485 Parameter #: 9 Reset Module 1 Reset Module Value 0 1 2 Description Ready (default) Reset Module Set Defaults Figure 4.7 – Reset Screen on an LCD OIM When you enter 1 (“Reset Module”) the module is immediately reset. When you enter 2 (“Set Defaults”) the module sets all module parameters to their factory-default settings. The module should be reset after performing a “Set Defaults.
4.8 Viewing the Module Configuration The parameters in table 4.4 provide information about how the module is configured. You can view these parameters at any time. Table 4.4 – Module Configuration Status Parameters No. Name 01 DPI Port 02 DPI Data Rate 04 DF1 Addr Actual 06 DF1 Rate Actual 07 Ref/Fdbk Size 08 Datalink Size 11 Active Cfg 13 DPI I/O Active 25 26 CRC/BCC Act Dup Msg Detect 4-8 Description The port to which the module is connected. This will usually be port 5.
CHAPTER 5 Using VS Utilities on the RS485 Network Chapter 5 provides instructions for configuring VS Utilities (version 1.01 or higher) to access SP600 drives on the RS485 network. Figure 5.1 shows a typical RS485 DF1 network. PC Running VS Utilities RECOMM-232 Serial Converter Module SP600 Drives Figure 5.1 – Typical RS485 DF1 Network To connect to the network using VS Utilities: Step 1. Select Explore > Connect > Network as shown in figure 5.2. VS Utilities Figure 5.
Step 2. Select Single to connect to a single node on the network. Select Multiple to connect to multiple nodes and enter the node range (figure 5.3). “Offline” or “Online” text will be displayed next to the number to show if the particular node is present on the network. In this example, two nodes with DF1 addresses of 1 and 2 will be accessed. Figure 5.3 – Node Selection Screen: Multiple Nodes Selected Step 3. Click Connect.
Step 4. Click on each node to have VS Utilities perform a device read as shown in figure 5.5. A “+” will appear to the left of the node upon completion. VS Utilities Node 1: - SP600 Node 2: - SP600 Figure 5.5 – Result of Device Read Performed by VS Utilities Step 5. Click on the “+” for each node to expand the information as shown in figure 5.6. VS Utilities Node 1: - SP600 0 - SP600 240V 4.
Step 6. Click on the desired item to access its parameters as shown in figure 5.7. VS Utilities Node 1: - SP600 0 - SP600 240V 4.2A 1 - LCD OIM 2 - RECOMM-232 RS232 DF1 5 - RECOMM-485 RS485 DF1 Node 2: - SP600 0 - SP600 240V 4.2A 1 - LCD OIM 5 - RECOMM-485 RS485 DF1 Figure 5.
CHAPTER 6 Troubleshooting the Module and Network Chapter 6 contains information for troubleshooting the RS485 DF1 module and the network. 6.1 Understanding the Status Indicators The module has four status indicators. They can be viewed on the module or through the drive cover. (See figure 6.1.) ➀ ➁ ➂ ➃ ➀ ➁ ➂ ➃ Number Status Indicator Description Refer to... ➀ DRIVE DPI Connection Status Section 6.1.1 ➁ MS Module Status Section 6.1.2 ➂ NET A DF1 Status Section 6.1.
6.1.1 DRIVE Status Indicator Table 6.1 – DRIVE Status Indicator: State Definitions Status Off Cause The module is not powered or is not connected properly to the drive. Flashing The module is not Red receiving a ping message from the drive. Solid Red Securely connect the module to the drive using the Internal Interface cable. • • Apply power to the drive. • Cycle power to the drive. Verify that cables are securely connected.
6.1.2 MS Status Indicator Table 6.2 – MS Status Indicator: State Definitions Status Off Cause The module is not powered. Flashing The module has Red failed the firmware test. Solid Red The module has failed the hardware test. Flashing The module is Green operational but is not transferring I/O data. Solid Green The module is operational and transferring I/O data.
6.1.3 NET A Status Indicator Table 6.3 – NET A Status Indicator: State Definitions Status Off Flashing Green 6-4 Cause The module is not powered or the module is not properly connected to the network. The module is properly connected, but it is not communicating with any devices on the network. Corrective Actions • Securely connect the module to the drive using the Internal Interface cable. • Correctly connect the RS485 cable to the DF1 plug. • • Apply power to the drive.
6.1.4 NET B Status Indicator Table 6.4 – NET B Status Indicator: State Definitions Status Off Flashing Green 6.2 Cause The module is not receiving data over the network. The module is receiving data over the network. Corrective Actions • Place the controller in RUN, or apply power to the peer device that will send I/O. • Program a controller peer device to recognize and transmit I/O to the module. • Configure the module for the program in the controller or the I/O from the peer device.
Table 6.5 – Module Diagnostic Items (Continued) No. Event Description 7 8 9 10 11 12 13 14 Datalink A1 In Datalink A2 In Datalink B1 In Datalink B2 In Datalink C1 In Datalink C2 In Datalink D1 In Datalink D2 In The current value of the specified Datalink In being transmitted to the host by the module. If the module has not enabled the Datalink, the value is 0.
Table 6.5 – Module Diagnostic Items (Continued) No. Event Description 34 PCCC I/O Timeout The I/O communication timeout value (secs) before the action selected in module parameter 10 (Comm Flt Action) is taken. 35 Data Rate SW 36 Node Address SW The value of the Node Address switch on the module. 6.3 The value of the Data Rate switch on the module. Viewing and Clearing Events The module maintains an event queue that reports the history of its actions.
Events Many events in the event queue occur under normal operation. If you encounter unexpected communications problems, the events may help you or Reliance Electric personnel troubleshoot the problem. Table 6.6 lists events that may appear in the event queue. Table 6.6 – Event Codes and Descriptions Code Event Description 1 No Event Empty event queue entry. 2 DPI Bus Off Flt A bus-off condition was detected on DPI. This event may be caused by loose or broken cables or by noise.
Table 6.6 – Event Codes and Descriptions (Continued) Code Event Description 20 Normal Startup The module successfully started up. 21 Message Timeout A Client-Server message sent by the peripheral was not completed. 22 DPI Fault Msg The DPI host has faulted. 23 DPI Fault Clear The DPI host transitioned from a faulted to a non-faulted state. 24 Flt Cfg Error At least one of the Fault Configuration parameters contains a value greater than 65535 and the DPI product expects a 16-bit value.
6-10 RS485 DF1 Communications Module
APPENDIX A Technical Specifications Communications Network Protocol Data Rates DF1 1200, 2400, 4800, 9600, 19.2 K, 38.4 K, PGM If the Data Rate switch is set to “PGM,” the module will use the setting of module parameter 5 (DF1 Rate Cfg) for the data rate. Drive Protocol Data Rates DPI 125 K or 500 K Electrical Consumption Drive 150 mA at 5 VDC supplied through the drive Mechanical Dimensions Height Length Width 16 mm (0.625 in) 86 mm (3.34 in) 81 mm (3.
Regulatory Compliance A-2 UL 508C and CUL CE EN61800-3 RS485 DF1 Communications Module
APPENDIX B RS485 DF1 Module Parameters The following information is provided for each module parameter along with its description: Parameter Number: Unique number assigned to each parameter. Parameter Name: Unique name assigned to each parameter. Range: Predefined parameter limits or selections. Default: Factory default setting. Type: Read Only or Read/Write. Reset Required: Module must be reset before parameter value is recognized.
1 DPI Port Range: 0 to 7 Default: 5 Type: Read Only Reset Required: N/A Displays the port to which the module is connected. This will usually be port 5. 2 DPI Data Rate Range: 0 = 125 Kbps 1 = 500 Kbps Default: 0 = 125 Kbps Type: Read Only Reset Required: N/A Displays the data rate used by the drive. This rate is set in the drive and the module detects it.
5 DF1 Rate Cfg Range: 0 = 1200 bps 1 = 2400 bps 2 = 4800 bps 3 = 9600 bps 4 = 19.2 kbps 5 = 38.4 kbps Default: 3 = 9600 bps Type: Read/Write Reset Required: Yes Sets the DF1 data rate if the Data Rate switch on the module is set to “PGM” (Program). 6 DF1 Rate Actual Range: 0 = 1200 bps 1 = 2400 bps 2 = 4800 bps 3 = 9600 bps 4 = 19.2 kbps 5 = 38.4 kbps Default: 3 = 9600 bps Type: Read Only Reset Required: Yes Displays the DF1 data rate actually used by the module.
9 Reset Module Range: 0 = Ready (No action) 1 = Reset Module 2 = Set Defaults (Restores module to factory-default settings) Default: 0 = Ready Type: Read/Write Reset Required: No This parameter is a command. It resets the module if set to “Reset Module.” It restores the module to factory default settings if set to “Set Defaults.” No action is taken if set to “Ready.” The parameter resets to “0 = Ready” after the command is performed.
11 Active Cfg Range: 0 = Switches 1 = EEPROM Default: 0 = Switches Type: Read Only Reset Required: N/A Displays the source from which the module node address and data rate are taken. This will either be switches on the module or parameters in EEPROM. The source is determined by the settings of the switches on the module. See chapter 3, Installing the RS485 DF1 Module, for more information about the switches. 12 DPI I/O Cfg Range: See figure B.1.
13 DPI I/O Active Range: See figure B.2. Default: xxx0 0001 Type: Read Only Reset Required: N/A No t No Used t No Used tU Da sed ta Da link D t Da alink tali C Da nk B ta Cm link A d/R ef Displays the I/O that the module is actively transmitting. The value of this parameter will usually be equal to the value of module parameter 12 (DPI I/O Cfg). See figure B.2. x x x 0 0 0 0 1 7 6 5 4 3 2 1 0 1 = I/O Enabled 0 = I/O Disabled x =Not Used Figure B.
16 17 18 19 20 21 22 23 Flt Cfg A1 Flt Cfg A2 Flt Cfg B1 Flt Cfg B2 Flt Cfg C1 Flt Cfg C2 Flt Cfg D1 Flt Cfg D2 Range: 0 to 4294967295 Default: 0 Type: Read/Write Reset Required: No Sets the data that is sent to the Datalink in the drive if module parameter 10 (Comm Flt Action) is set to “Send Flt Cfg” and communications are disrupted. Important: If the drive uses a 16-bit Reference, the most significant word of this value must be set to zero (0) or a fault will occur.
26 Dup Msg Detect Range: 0 = Disable 1 = Enable Default: 1 = Enable Type: Read/Write Reset Required: No Enables/disables duplicate message detection by the module. Normally, this is set to “Enable” (default). Set to “Disable” if using a ProSoft 3150-DFM module or any device that does not increment the TNS (transaction number) ID.
APPENDIX C Logic Command/ Status Words Appendix C provides the definitions of the Logic Command/Logic Status words that are used for some products that can be connected to the RS485 DF1 module. If you do not see the Logic Command/Logic Status for the product that you are using, refer to your product’s documentation. C.
Logic Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command x x x x 1 Description Reference Select 000 = No Command 001 = Ref. 1 (Ref A Select) 010 = Reserved 011 = Ref. 3 (Preset 3) 100 = Ref. 4 (Preset 4) 101 = Ref. 5 (Preset 5) 110 = Ref. 6 (Preset 6) 111 = Ref. 7 (Preset 7) MOP Decrement 0 = Not Decrement 1 = Decrement A 0 = Not Stop condition (logic 0) must first be present before a 1 = Start condition will start the drive.
Logic Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 x x x x Logic Command/Status Words Status Reference Description 0000 = Ref A Auto 0001 = Reserved 0010 = Preset 2 Auto 0011 = Preset 3 Auto 0100 = Preset 4 Auto 0101 = Preset 5 Auto 0110 = Preset 6 Auto 0111 = Preset 7 Auto 1000 = Term Blk Manual 1001 = DPI 1 Manual 1010 = DPI 2 Manual 1011 = DPI 3 Manual 1100 = DPI 4 Manual 1101 = DPI 5 Manual 1110 = DPI 6 Manual 1111 = Jog Ref C-3
C-4 RS485 DF1 Communications Module
GLOSSARY BCC (Block Check Character) - A technique for error detection in data communications. A character is added to a transmission block, which is compared with a second BCC computer by the receiver to determine if the transmission is error free. controller - Also called programmable logic controller.
DPI product - A device that uses the DPI communications interface to communicate with one or more peripheral devices. For example, a motor drive such as a SP600 drive is a DPI product. In this manual, a DPI product is also referred to as “product” or “host.” fault action - Determines how the module and connected product act when a communications fault (for example, a cable is disconnected) occurs or when the scanner is switched out of run mode.
module - Devices such as drives, controllers, and computers usually require a module to provide a communication interface between them and a network such as RS485 DF1. An module reads data on the network and transmits it to the connected device. It also reads data in the device and transmits it to the network. The RS485 DF1 module connects SP600 drives to an RS485 DF1 network. Modules are sometimes also called “adapters,” “cards,” “embedded communication options,” “gateways,” and “peripherals.
Type 0/Type 1/Type 2 Control - When transmitting I/O, the module can use different types of messages for control. The Type 0, Type 1, Type 2 control events help Reliance Electric personnel identify the type of message that a module is using. transaction number (TNS) - A two-byte field in a DF1 message packet that is used in combination with the SRC (source node of the message) and CMD (command code) bytes to uniquely identify every message packet.
INDEX A E Active Cfg (11), B-5 assistance, technical, 1-2 error-checking method, setting, 4-3 events codes and descriptions, 6-8 viewing and clearing, 6-7 B BCC (Block Check Character), 4-3 F C fault action, setting, 4-5 fault configuration parameters, setting, 4-6 Flt Cfg A1 (16), B-7 Flt Cfg A2 (17), B-7 Flt Cfg B1 (18), B-7 Flt Cfg B2 (19), B-7 Flt Cfg C1 (20), B-7 Flt Cfg C2 (21), B-7 Flt Cfg D1 (22), B-7 Flt Cfg D2 (23), B-7 Flt Cfg Logic (14), B-6 Flt Cfg Ref (15), B-6 checklist, installation,
module applying power to, 3-7 components, 2-1 configuration, viewing, 4-8 configuring, 4-1 to 4-8 connecting to drive, 3-3 connecting to network, 3-6 diagnostic items, 6-5 dimensions, A-1 features, 1-1 installing, 3-1 to 3-7 parameters, B-1 to B-8 resetting, 4-6 specifications, A-1 troubleshooting, 6-1 to 6-9 MS status indicator, 6-3 P parameter descriptions, B-1 to B-8 power consumption, A-1 power, applying to module, 3-7 protocol, A-1 publications, related, 1-2 R Ref/Fdbk Size (7), B-3 regulatory compli
U.S. Drives Technical Support Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: support@drives.ra.rockwell.com, Online: www.ab.com/support/abdrives Publication D2-3514 – August 2002 Copyright © 2002 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.